Cable Derating Factors: Ambient Temperature, Grouping and Installation Conditions

— A Practical Guide for Engineers, EPCs, and Project Teams

Cable current-carrying capacity tables published in IEC 60364-5-52, IEC 60502, and other standards are calculated under specific reference conditions: a defined ambient temperature, a single circuit in isolation, and—for buried cables—a defined soil thermal resistivity and burial depth. Real installations almost never match these reference conditions exactly. Cables are grouped in trays, run through hot process areas, buried in dry soil, or installed at depths greater than the reference.-4-26

When installation conditions are less favourable than the reference, the cable must be derated—its tabulated current rating reduced—to prevent overheating, insulation degradation, and premature failure. This guide explains the derating factors that engineers must apply, how they compound, and the practical consequences of getting them wrong.-8


1. The Derating Equation

The effective current-carrying capacity of a cable under actual installation conditions is:

Iz=Itab×Ca×Cg×Cs×Cd×Ci

Where:

SymbolFactorApplies When
IzEffective (derated) current rating (A)—
ItabTabulated rating at reference conditions (A)—
CaAmbient temperature correction factorAir or ground temperature ≠ reference
CgGrouping (mutual heating) factorMultiple loaded circuits in proximity
CsSoil thermal resistivity factorBuried cables; soil resistivity ≠ reference
CdDepth of burial factorBuried cables; depth ≠ reference
CiThermal insulation factorCable in contact with building insulation

The critical point: these factors multiply. Two factors of 0.80 each produce a combined factor of 0.64—not 0.60. Individually modest derating can compound to require a substantially larger cable.-26

The cable must be selected such that its tabulated rating meets or exceeds the required value:

Itab≥InCa×Cg×Cs×Cd×Ci

Where In is the protective device rating.-8


2. Ambient Temperature Correction Factor (Ca)

Why it matters: A cable's current rating is limited by its maximum conductor operating temperature—typically 70°C for PVC insulation and 90°C for XLPE. If the ambient temperature is higher than the reference, there is less temperature “headroom” for the cable's own I²R heating, so it must carry less current.-26

2.1 Reference Temperatures by Standard

StandardReference Ambient (Air)Reference Ambient (Ground)
IEC 60364-5-5230°C20°C
BS 767130°C20°C
AS/NZS 300840°C25°C
NEC30°C—

Source: ECalPro comparison of reference conditions.-8

2.2 IEC 60364-5-52 Table B.52.14 (Air)

Ambient Temp (°C)PVC (70°C max)XLPE (90°C max)
101.221.15
201.121.08
301.001.00
400.870.91
500.710.82
600.500.71

Source: IEC 60364-5-52 Table B.52.14.-4

Interpretation: At 50°C ambient, a PVC-insulated cable retains only 71% of its 30°C rating. A cable rated 100 A in the table delivers only 71 A in practice. XLPE, with its higher maximum conductor temperature, retains 82%—but still loses nearly one-fifth of its capacity.

2.3 The Underlying Formula

The ambient temperature factor is derived from the allowable temperature rise:

Ca=Tmax−TactualTmax−Treference

Where Tmax is the maximum conductor temperature (70°C for PVC, 90°C for XLPE), Tactual is the actual ambient temperature, and Treference is the reference ambient temperature (30°C air, 20°C ground).-8

Engineering consequence: The square-root relationship means that derating accelerates as ambient temperature approaches the insulation limit. A cable that appears adequately sized at 30°C may be severely overloaded at 55°C.


3. Grouping Correction Factor (Cg)

Why it matters: When multiple loaded cables share the same route—bunched in conduit, stacked in a tray, or buried side by side—they heat each other. The mutual heating reduces each cable's ability to dissipate its own heat, so the group must be derated.-4

3.1 Grouping Tables in IEC 60364-5-52

IEC 60364-5-52 provides four separate grouping tables depending on the installation arrangement:

TableArrangement
B.52.17Cables bunched in conduit or enclosed in trunking
B.52.18Single layer on a wall or floor (cables touching)
B.52.19Single layer on a perforated or solid tray
B.52.20Buried cables — multiple circuits

Source: ECalPro.-4

3.2 Illustrative Grouping Factors

For cables bunched in air (touching, on a surface, embedded, or enclosed), typical factors are:

Number of CircuitsCorrection Factor
11.00
20.80
30.70
40.65
50.60
60.57

Source: IEC 60364-5-52 Table B.52.17, as reproduced in multiple references.

Interpretation: Six circuits bunched together retain only 57% of their individual rating. A cable that would carry 100 A alone carries only 57 A when grouped with five others. This is one of the most consequential derating factors in industrial installations, where cable trays are routinely densely packed.

3.3 Important Caveats

  • Grouping factors apply only to loaded circuits. A cable carrying no current does not contribute to mutual heating and should not be counted.

  • Spacing matters. Cables with spacing between them derate less severely than cables in direct contact. The tables distinguish between touching and spaced arrangements.

  • Buried cables have separate grouping tables. Direct-buried circuits derate differently from cables in air.


4. Soil Thermal Resistivity Factor (Cs)

Why it matters: For buried cables, the soil is the heat sink. Soil thermal resistivity (measured in K·m/W) determines how effectively heat is conducted away from the cable. Dry, sandy, or rocky soil has high resistivity (poor thermal conductivity) and requires more derating than moist, loamy soil.

4.1 Reference Conditions

Standard / SourceReference Soil Thermal Resistivity
IEC 60502-22.5 K·m/W (some tables) or 1.5 K·m/W (others)
Prysmian MV rating1.5 K·m/W
ABB2.5 K·m/W

Caution: The reference value varies between standards and manufacturers. Always verify which reference applies to the specific tabulated rating being used.-21

4.2 Illustrative Soil Resistivity Factors (Direct Buried)

For a reference resistivity of 1.5 K·m/W, typical factors for single-core cables are:

Soil Resistivity (K·m/W)Factor (16 mm²)Factor (50 mm²)
0.71.291.32
1.01.151.16
1.51.001.00
2.50.820.81
3.00.750.75

Source: Prysmian MV cable rating factors.-21

Interpretation: At 2.5 K·m/W (a common value for dry soil), the cable retains approximately 81–82% of its reference rating. At 3.0 K·m/W (very dry or rocky soil), it retains only 75%.

Best practice: For critical cables, use the worst-case (driest) soil condition unless the cable is installed in selected backfill with known thermal properties.


5. Depth of Burial Factor (Cd)

Why it matters: The reference burial depth for IEC 60502-2 and many manufacturer tables is 0.8 m. At greater depths, the thermal resistance of the soil path to the surface increases, reducing heat dissipation and requiring derating.-21

5.1 Illustrative Depth Factors

Depth of Laying (m)Single-Core (<185 mm²)Three-Core
0.51.041.04
0.81.001.00
1.00.980.98
1.50.950.95
2.00.930.93
3.00.900.90

Source: Prysmian MV rating factors, IEC 60502-2.-21

Interpretation: At 2.0 m depth, the cable retains 93% of its 0.8 m rating. The effect is less severe than temperature or grouping, but it still compounds with the other factors.


6. Thermal Insulation Factor (Ci)

When a cable is in direct contact with building thermal insulation, its heat dissipation is severely restricted. IEC 60364-5-52 provides a factor (Table B.52.21) for this condition. In practice, this factor is often 0.5 or lower—a cable embedded in insulation may carry only half its free-air rating. This is a common cause of overheating in roof voids and insulated walls.-4


7. How the Factors Compound: A Worked Example

Consider a PVC-insulated, 4 mm², 3-core cable with a tabulated rating of 32 A at 30°C in free air (single circuit, no grouping).

Actual installation conditions:

  • Ambient temperature: 45°C (hot process area) → Ca=0.79

  • Grouped with 3 other circuits in a tray → Cg=0.65

  • No soil factors (air installation) → Cs=1.00, Cd=1.00

  • Not in contact with insulation → Ci=1.00

Iz=32×0.79×0.65=32×0.5135=16.4 A

Result: The cable carries 16.4 A—just over half its tabulated rating. If the load is 20 A, the 4 mm² cable is inadequate and a larger size is required.

The engineering lesson: The compounding effect is not intuitive. Each factor alone appears manageable; together they can halve the effective capacity of a cable.


8. Common Mistakes to Avoid

MistakeConsequencePrevention
Applying only one factorSignificant overestimation of capacityApply all applicable factors multiplicatively
Using the wrong reference temperatureIncorrect Ca; cable overloadedVerify whether the tabulated rating is based on 30°C, 40°C, or another reference
Counting unloaded cables in groupingOver-derating; unnecessarily large cableCount only circuits carrying current
Using a single soil resistivity for all routesInaccurate deratingMeasure or obtain route-specific soil data; use worst-case
Ignoring burial depthOverestimation of capacity in deep trenchesApply Cd where depth ≠ 0.8 m
Forgetting thermal insulationSevere overheating in insulated walls/roofsApply Ci; route cables outside insulation
Assuming XLPE and PVC derate identicallyIncorrect factor selectionUse insulation-specific tables; XLPE derates less than PVC at high temperature
Not documenting derating calculationsNo traceability; errors undetectedRecord Itab, each factor, and Iz for each circuit

9. Why Choose Anhui Tiankang for Cable Selection?

Anhui Tiankang (Group) Co., Ltd. has nearly five decades of experience in industrial cable manufacturing. We provide the data and engineering support that allow EPCs to apply derating factors correctly and select cables with confidence.

SupportDetail
Clear tabulated ratingsReference conditions stated explicitly on datasheets
Construction-specific derating dataPVC, XLPE, LSZH, armoured, and fire-resistant cables with applicable correction factors
Engineering assistanceDerating calculations, cable sizing verification, and installation condition assessment
Complete product rangePower, instrumentation, control, and fire-resistant cables with consistent documentation

Core advantages:

  • Complete certifications: CCC Ex, ATEX, IECEx, SIL, CCS marine

  • CNAS-accredited laboratory: full electrical and thermal performance testing

  • Long-term supplier to CNPC, Sinopec, CNOOC, and international EPC projects

  • One-stop supply: from cables to glands to installation accessories


10. Conclusion

Cable derating is not a single calculation—it is a chain of multiplicative factors that reflect the reality of the installation. Ambient temperature, grouping, soil thermal resistivity, burial depth, and thermal insulation each reduce the effective capacity of the cable. Applied together, they can halve—or worse—the current a cable can safely carry.

Key takeaways:

FactorSymbolWhen It AppliesTypical Range
Ambient temperatureCaAir or ground temp ≠ reference1.22 (cold) to 0.50 (hot, PVC)
GroupingCgMultiple loaded circuits1.00 (single) to 0.57 (6 bunched)
Soil resistivityCsBuried cables; soil ≠ reference1.29 (wet) to 0.75 (dry/rocky)
Burial depthCdDepth ≠ 0.8 m1.04 (shallow) to 0.90 (3 m)
Thermal insulationCiCable in contact with insulationOften ≤0.5

The most important rule: Never select a cable from a table without confirming that the reference conditions match the actual installation. If they do not—and they rarely do—apply every applicable factor, and apply them multiplicatively.

Remember: A cable that is correctly derated for its installation conditions will deliver its rated life. A cable that is selected from a table without derating may appear to work at commissioning—and fail months or years later, when the insulation has been degraded by sustained overheating that was never visible on the surface.